More operations

Predictive maintenance software that starts with condition rules

Predictive maintenance software watches the condition of equipment, such as vibration, temperature, current and pressure, and raises a work order before a likely failure rather than after it. Most sites should start with condition rules written by their own engineers and add machine learning only when the data supports it. We build the data connections, rules, alerts and work-order links, and we are plain about the data you need first.

Book a workflow review

Four ways to maintain a machine

ApproachWhen work happensFits
ReactiveAfter a failureCheap, non-critical items with a spare on the shelf
PreventiveOn a calendar or run-hour scheduleWear that follows usage closely, such as filters and belts, and inspections required on a schedule
Condition-basedWhen a measured value crosses a limitEquipment with a measurable sign of wear, such as bearing temperature
PredictiveWhen trends or a model show failure is likely soonCritical equipment with good data and a known failure pattern

Predictive maintenance does not replace the others. It works in the interval between the moment a developing fault becomes detectable and the moment the machine fails, which reliability engineers draw as the P-F curve. The earlier a fault is detected, the more time planners have to order parts and book a shutdown. See the glossary entry on predictive maintenance for the short definition.

The data you need before machine learning

This is the honest part. A model learns from examples, and most sites are short of them. Before any machine learning, check:

  1. An asset register with a hierarchy and criticality: which pump is which, what it serves, and what a failure costs in downtime, safety and repair.
  2. Work orders with failure codes. If most say 'repaired' in free text, the history cannot tell which failures happened. Clean codes on the critical assets are often the first fix.
  3. Enough failures of the same kind. Well-maintained equipment fails rarely, which is good for the plant and bad for a model. One bearing failure in three years is not a training set.
  4. Signals at the right rate. Bearing defects show in vibration measured thousands of times a second; a temperature averaged every fifteen minutes by a building management system will not see them.
  5. Operating context: load, speed, running or stopped, so a machine that is switched off is not flagged for a sudden drop in vibration.
  6. Clocks that agree. Timestamps from sensors, the historian and the maintenance system aligned to one time zone.

If several are missing, start with rules on the assets whose data is good, and fix the data while the rules run. Our article on preparing your data for AI and our data integration work cover how.

Condition rules engineers can read

Rules capture what your engineers already know, and they are predictable and testable. Good rules combine signals and require persistence, so one noisy reading does not raise an alarm:

  • Bearing temperature above the manufacturer's limit for more than ten minutes while the motor is running.
  • Vibration rising steadily over two weeks at constant load, even while it is still below the alarm level.
  • Motor current up while pump flow is unchanged, which can point to friction or a mechanical fault.
  • Pressure difference across a filter above its change point.
  • Run hours or start counts reaching a service interval.

Engineers change thresholds in a screen, not in code, and every change is versioned with who made it and why. Once months of normal operation are recorded across the seasons (a chiller in a Gulf summer works very differently from the same chiller in winter), anomaly detection can flag patterns no rule describes. Models that estimate remaining useful life come last, and only for failure modes with enough history.

From alert to work order, and back

An alert nobody acts on is noise, and too much noise teaches people to ignore alerts. Each alert follows a fixed path:

  1. It reaches a reliability engineer's or planner's queue with the asset, the rule, a chart of the data and the asset's recent work orders.
  2. They dismiss it with a reason, keep watching it, or raise a work order.
  3. The work order is created in your computerised maintenance management system (CMMS) through its API, with the symptom, a suggested inspection and a priority.
  4. The technician records what was found, with a failure code, on a mobile screen in Arabic or English.
  5. That finding marks the alert as confirmed or false, which is how rules are tuned and, later, how a model gets labelled examples.

Alerts are suppressed during planned shutdowns, and each asset has an alert budget: a rule that fires too often is reviewed, not tolerated. A language model can draft the work order description from the alert and pull the relevant pages of the manufacturer's manual through a knowledge assistant. It never closes an alert or changes a rule on its own.

Keeping the control network out of reach

Condition data often comes from the network that runs the plant: PLCs, SCADA, a data historian or a building management system. That network matters more than any dashboard, so our designs follow a few rules:

  • Read only, one way. Data leaves the control network through a gateway or a historian copy in a separate network zone. The maintenance software never writes to a controller and cannot start or stop a machine.
  • Standard protocols such as OPC UA or MQTT, with authentication and encryption switched on.
  • Gateways treated as servers: a named owner, patching, unique credentials and no default passwords.
  • A threat model before connection, covering who could reach the gateway and what they could do from it.

Industrial security has its own standards, such as the IEC 62443 series for industrial automation and control systems. We design with awareness of them and of your site's rules, and work with your control engineers, who keep authority over the control network. Our cybersecurity service covers the review.

Judging the pilot over months, not weeks

Failures are rare, so results take time to read. Pick a small group of critical assets with a known failure pattern and record a baseline: unplanned downtime, emergency work orders, maintenance cost and mean time between failures on those assets, plus how often preventive work is done on schedule. After launch, add alert quality: the share of alerts that led to a confirmed finding, and failures that arrived without an alert. Plan to judge the pilot over months, and tell whoever funds it so at the start.

How a predictive maintenance project usually starts

We start with a data audit inside a discovery sprint: which sensors and systems exist, what the maintenance history holds, which assets are critical, and how data can leave the control network safely. You receive a roadmap naming the pilot assets, the first rules, the data fixes and the CMMS integration. Then we build the pilot with weekly demos, as part of our AI agents and automation service. In buildings, the maintenance request history is often the first source of failure records.

A small first step

A 30-minute workflow review

Pick one process that costs your team time. We look at it with you and tell you honestly whether automation or an AI agent pays, what it would take, and what to measure first.

Message us on WhatsApp

Questions we get asked

  • Not always. Many sites already collect useful data in a PLC, a historian or a building management system, such as temperatures, pressures, current and run hours, and the audit shows what exists. New sensors, usually vibration sensors on critical rotating equipment, are added where a known failure mode cannot be seen in the current data.

  • There is no single figure. Anomaly detection needs months of normal operation covering the seasons and operating modes, and predicting a specific failure needs several recorded examples of it, with dates and causes. Rules need neither, which is why we start with them and add models when the history supports it.

  • We design it not to. The maintenance software reads data and raises alerts and work orders; it never writes to controllers. Protective trips belong in the control and safety systems, which your control engineers own and test. Keeping the two apart means a fault in the maintenance software cannot stop your plant.

  • Sometimes not. If a failure is cheap, quick to repair and a spare is on the shelf, preventive or even reactive maintenance may be the sensible choice. Predictive methods pay off on critical equipment where a failure stops production, damages other equipment or creates a safety risk, and a criticality ranking shows where that is.

  • Usually. Most maintenance management systems have an API or an import route for assets and work orders, and the alert workflow creates work orders there so planners keep one backlog. Where the API is limited, a scheduled import or an email-to-work-order route can bridge the gap until a better connection is in place.

Keep exploring

Ready to build something secure?

Tell us about your product. We will reply with a clear plan.

Start a project

We would like to use Microsoft Clarity to see how visitors use the site, so we can improve it. It sets cookies and is off unless you accept. Cookie policy